2 pipe system
Specifications | Units | Speed | MC-SG-200T2 | MC-SG-400T2 | MC-SG-600T2 | MC-SG-800T2 |
Air flow rate | Supermax | 250 | 390 | 510 | 620 | |
Max (*) | 180 | 315 | 450 | 540 | ||
m3/h | Med (*) | 120 | 230 | 350 | 450 | |
Min (*) | 80 | 155 | 240 | 310 | ||
Static | 10 | 18 | 25 | 32 | ||
Total cooling capacity | Supermax | 1.19 | 2.12 | 2.90 | 3.73 | |
Max | 0.88 | 1.81 | 2.70 | 3.38 | ||
kW | Med | 0.79 | 1.45 | 2.20 | 2.75 | |
Min | 0.45 | 0.98 | 1.70 | 2.13 | ||
Sensible capacity | Supermax | 0.87 | 1.56 | 2.16 | 2.97 | |
Max | 0.69 | 1.35 | 2.00 | 2.70 | ||
kW | Med | 0.60 | 1.10 | 1.68 | 2.30 | |
Min | 0.30 | 0.70 | 1.25 | 1.70 | ||
Heating capacity | Supermax | 1.55 | 2.71 | 3.71 | 4.71 | |
Max | 1.10 | 2.40 | 3.20 | 4.23 | ||
kW | Med | 0.90 | 1.50 | 2.40 | 3.40 | |
Min | 0.61 | 1.16 | 1.75 | 2.41 | ||
V/H/Ph | 230 V – 50 Hz - 1Ph | |||||
Motor input | Supermax | 20 | 22 | 24 | 27 | |
Max | 12 | 13 | 14 | 17 | ||
W | Med | 5 | 6 | 7 | 10 | |
Min | 3 | 4 | 5 | 8 | ||
Water flow rate | Supermax | 204 | 364 | 498 | 639 | |
Max | 151 | 311 | 463 | 580 | ||
l/h | Med | 136 | 249 | 377 | 472 | |
Min | 77 | 168 | 292 | 365 | ||
Pressure drop | Supermax | 15.1 | 10.2 | 20.9 | 19.9 | |
Max | 13.1 | 8.2 | 19.0 | 18.7 | ||
kPa | Med | 7.2 | 6.0 | 16.5 | 13.2 | |
Min | 4.1 | 4.1 | 13.0 | 10.0 | ||
Coil connection | 1/2” GF | 1/2” GF | 1/2” GF | 1/2” GF | ||
Water content | L | 0,33 | 0,59 | 0,85 | 1,11 | |
Sound power | Supermax | 55.0 | 56.0 | 57.1 | 58.3 | |
Max | 51.3 | 52.2 | 52.4 | 53.3 | ||
dB(A) | Med | 44.6 | 45.5 | 46.6 | 48.6 | |
Min | 37.5 | 38.6 | 40.5 | 38.7 | ||
Sound pressare | Supermax | 38.0 | 39.0 | 40.1 | 41.3 | |
Max | 34.3 | 35.2 | 35.4 | 36.3 | ||
dB(A) | Med | 27.6 | 28.5 | 29.6 | 31.6 | |
Min | 20.5 | 21.6 | 23.5 | 21.7 |
COOLING MODE
Room:27° C – 47% R.H. Water temp. (in/out):7/12°C
HEATING MODE
Room:20° C. Water temp. in:50.
(*) Declared values are relative to standard settings at 1500, 900 and 600 RPM. It is always possible to change the air flow, changing dip switch setting in the PCB.
Specifications | Units | MC-SG-200T2 | MC-SG-400T2 | MC-SG-600T2 | MC-SG-800T2 |
A | mm | 681 | 873 | 1065 | 1257 |
Net weight | kg | 14 | 18 | 21 | 25 |
Gross weight | kg | 18 | 21 | 25 | 29 |
Specifications | Units | MC-SG-200T2 | MC-SG-400T2 | MC-SG-600T2 | MC-SG-800T2 |
A | mm | 681 | 873 | 1065 | 1257 |
Net weight | kg | 14 | 18 | 21 | 25 |
Gross weight | kg | 18 | 21 | 25 | 29 |