fan coil units
MCFC series

This type of concealed fan coil unit is installed behind a false ceiling, thus having almost no effect on the interior. The low static pressure of the fan prevents the use of long ducts. As a rule, the intake and exhaust of air is carried out directly through the grilles
Low  ESP duct<br/> fan coil units<br/> MCFC series

Low pressure fan coil units, due to their low noise level, are widely used in hotels, residential areas and small offices.

1,2 ... 12,6 kW
Cooling capacity :
1,8 ... 18,9 kW
Heating capacity :
Features and advantages:
Features and advantages:
  • Optimized heat exchanger with increased heat exchange area ensures high fan coil efficiency.
  • Centrifugal fan with metal blades and galvanized steel casing ensure high reliability and fire resistance.
  • The compact arrangement of the centrifugal fan in the housing reduces air friction loss, ensures more efficient and quiet operation of the unit.
  • Drain pan with an inclination ensures safe and complete drainage of condensate from its lowest point.
  • It is possible to choose the position of the air intake during installation: from the rear or from  the bottom.
  • Available static pressure up to 30 Pa.
  • Low power consumption.
  • Low noise level.

 

 

Fan coil thermostat Mycond Block
Fan coil thermostat Mycond  TRF-B2 white /black
Fan coil thermostat Mycond ORB Fan
The optimal set of automation for affordable and simple control by smartphone

2-pipe fan coil units. Specifications

 

Specifications Units MCFC02 MCFC03 MCFC04 MCFC05 MCFC06
Air flow rate, H/M/L

m3/h

340/255/170 510/382/255 680/510/340 850/638/425 1020/765/510
Cooling capacity, H/M/L kW 1,8/1,5/1,2 2,7/2,3/1,8 3,6/3,1/2,4 4,5/3,8/2,9 5,4/4,6/3,5
Heating capacity, H/M/L kW 2,7/2,3/1,8 4,0/3,5/2,7 5,4/4,6/3,5 6,8/5,8/4,4 8,1/6,9/5,3
Power consumption, speed – H W 44 57 71 87 107
Static pressure Pa 30 30 30 30 30
Noise level, speed – H dB(A) 40 42 44 46 47
Water flow rate

m3/h

0,35 0,61 0,8 0,95 1,08
Water pressure drop kPa 30 30 30 30 40
Fan type   Centrifugal fan with forward-curved blades
Motor type   Four-speed induction fan motor
Insulation   Class Е Class Е Class Е Class Е Class Е
Power supply V/phases 220-230 V / 50 or 60 Hz / 1 phase
Heat exchanger type   Copper pipe with aluminium fins
Number of rows   2 2 2 2 2
Max. operating pressure Pa 1,6 1,6 1,6 1,6 1,6
Inlet/outlet water pipe mm Rc3/4”(DN20) Rc3/4”(DN20) Rc3/4”(DN20) Rc3/4”(DN20) Rc3/4”(DN20)
Condensate pipe mm R3/4”(DN20) R3/4”(DN20) R3/4”(DN20) R3/4”(DN20) Rc3/4”(DN20)
Unit dimensions (WxDxH) mm 694х518х240 894х518х240 894х518х240 1039х518х240 1129х518х240
Package dimensions (WxDxH) mm 715х260х545 915х260х545 915х260х545 1060х260х545 1150х260х545
Unit weight kg 12,6 16,4 16,8 18,9 20,2
Packed weight kg 14,6 18,9 19,4 21,9

23,7

 

Specifications Units MCFC08 MCFC10 MCFC12 MCFC14
Air flow rate, H/M/L

m3/h

1360/1020/680 1700/1275/850 2040/1530/1020 2380/1785/1190
Cooling capacity, H/M/L kW 7,2/6,2/4,7 9,0/7,7/5,9 10,8/9,2/7,1 12,6/10,8/8,2
Heating capacity, H/M/L kW 10,8/9,2/7,1 13,5/11,5/8,8 16,2/13,8/10,5 18,9/16,1/12,3
Power consumption, speed – H W 156 174 212 253
Static pressure Pa 30 30 30 30
Noise level, speed – H dB(A) 48 50 52 54
Water flow rate

m3/h

1,39 1,56 1,92 2,25
Water pressure drop kPa 40 40 40 50
Fan type   Centrifugal fan with forward-curved blades
Motor type   Four-speed induction fan motor
Insulation   Class Е Class Е Class Е Class Е
Power supply V/phases 220-230 V / 50 or 60 Hz / 1 phase
Heat exchanger type   Copper pipe with aluminium fins
Number of rows   3 3 3 3
Max. operating pressure Pa 1,6 1,6 1,6 1,6
Inlet/outlet water pipe mm Rc3/4”(DN20) Rc3/4”(DN20) Rc3/4”(DN20) Rc3/4”(DN20)
Condensate pipe mm R3/4”(DN20) R3/4”(DN20) R3/4”(DN20) R3/4”(DN20)
Unit dimensions (WxDxH) mm 1319х518х240 1619х518х240 1719х518х240 1909х518х240
Package dimensions (WxDxH) mm 1340х260х545 1640х260х545 1740х260х545 1930х260х545
Unit weight kg 26 31,3 33,4 35,6
Packed weight kg 30 35,8 38 41,1

 

Rated test conditions:
Cooling: inlet air temperature +27 °C DB / +19.5 °C WB, inlet water temperature +7 °C, outlet water temperature +12 °C.
Heating: inlet air temperature +21 °C, inlet water temperature +60 °C, the same water flow rate as in the cooling mode.
Sound pressure level has been measured in a sound insulated room, with a reference point at 1 m in front of and 1 m below the vertical axis of the unit.
The static pressure has been measured excluding the filter and the air outlet.

Installation methods
Installation methods
Dimensions
Dimensions

Dimensions of MCFC fan coil units

 

Model Units MCFC-02T2 MCFC-03T2 MCFC-04T2 MCFC-05T2 MCFC-06T2 MCFC-08T2 MCFC-10T2 MCFC-12T2 MCFC-14T2
A mm 487 687 687 832 922 1112 1412 1512 1702
B mm 523 723 723 868 958 1148 1448 1548 1738
C mm 669 869 869 1014 1104 1294 1594 1694 1884
D mm 522 722 722 867 957 1147 1447 1547 1737

 

 

 

 

 

 

    